MEANWELL SE Series Single Output Power Supply
Many In Stock
Ballast /Drivers
SE-100-24
S7
- AC input active surge current limiting
- AC input range selected by switch
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Forced air cooling by built-in DC ball bearing fan
- High power density 3w/inch3
- With DC_OK signal output
- Built-in remote ON-OFF control
- Built-in remote sense function
- UL / CUL approved
- Low cost
MODEL | SE-100-5 | SE-200-15 | SE-100-24/200-24/350-24 | SE-200-27/350-27 | SE-100-48 | |||
DC VOLTAGE | 5V | 15V | 24V | 27V | 48V | |||
RATED CURRENT | 20A | 14A | 4.5A/8.8A/14.6A | 7.8A/13A | 2.3A/12.5A | |||
CURRENT RANGE | 0 ~ 100A | 0 ~ 40A | 0 ~ 25A | 0 ~ 22.2A | 0 ~ 12.5A | |||
RATED POWER | 100W | 200W | 100W/200W/350W | 200W/350W | 100W/600W | |||
RIPPLE & NOISE (max.) Note.2 | 150mVp-p | 150mVp-p | 150mVp-p | 150mVp-p | 200mVp-p | |||
VOLTAGE ADJ. RANGE | 4.75 ~ 5.5V | 13.5 ~ 16.5V | 22 ~ 26.4V | 24 ~ 30V | 43 ~ 56V | |||
VOLTAGE TOLERANCE Note.3 | ±2.0% | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |||
OUTPUT | LINE REGULATION | ±0.5% | ±0.5% | ±0.5% | ±0.5% | ±0.5% | ||
LOAD REGULATION | ±2.0% | ±0.5% | ±0.5% | ±0.5% | ±0.5% | |||
SETUP, RISE TIME | 1000ms, 50ms/230VAC 1000ms, 50ms/115VAC at full load | |||||||
HOLD UP TIME (Typ.) | 20ms/230VAC 16ms/115VAC at full load | |||||||
VOLTAGE RANGE | 90 ~ 132VAC / 180 ~ 264VAC selected by switch 254 ~ 370VDC | |||||||
FREQUENCY RANGE | 47 ~ 63Hz | |||||||
EFFICIENCY (Typ.) | 78% | 83% | 84% | 87% | 87% | 87% | 88% | |
AC CURRENT (Typ.) | 12A/115VAC 7.5A/230VAC | |||||||
INRUSH CURRENT (Typ.) | 30A/115VAC 60A/230VAC | |||||||
LEAKAGE CURRENT | <2.0mA / 240VAC | |||||||
105 ~ 125% rated output power | ||||||||
OVERLOAD | Protection type : Shut down o/p voltage, re-power on to recover | |||||||
5.75 ~ 6.3V | 13.8 ~ 16.2V | 18 ~ 21V | 27.6 ~ 32.4V | 31 ~ 36.5V | 42 ~ 50V | 57.6 ~ 67.2V | ||
PROTECTION | OVER VOLTAGE | Protection type : Shut down o/p voltage, re-power on to recover | ||||||
OVER TEMPERATURE | Shut down o/p voltage, recovers automatically after temperature goes down | |||||||
WORKING TEMP. | -20 ~ +60℃ (Refer to output load derating curve) | |||||||
WORKING HUMIDITY | 20 ~ 90% RH non-condensing | |||||||
STORAGE TEMP., HUMIDITY | -40 ~ +85℃, 10 ~ 95% RH | |||||||
ENVIRONMENT | TEMP. COEFFICIENT | ±0.05%/℃ (0 ~ 50℃) | ||||||
VIBRATION | 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes | |||||||
SAFETY STANDARDS | UL60950-1,UL62368-1, EAC TP TC 004, BSMI CNS14336-1, KC K60950-1(for 12V,24V only) approved | |||||||
SAFETY & EMC | WITHSTAND VOLTAGE | I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC | ||||||
ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC | |||||||
MTBF | 197K hrs min. MIL-HDBK-217F (25℃) | |||||||
OTHERS | DIMENSION | 247*127*63.5mm (L*W*H) | ||||||
PACKING | 1.2Kg; 6pcs/13.4Kg |
MODEL |
SE-450-3.3 |
SE-450-5 |
SE-450-12 |
SE-450-15 |
SE-450-24 |
SE-450-36 |
SE-450-48 |
|
OUTPUT |
DC VOLTAGE |
3.3V |
5V |
12V |
15V |
24V |
36V |
48V |
RATED CURRENT |
75A |
75A |
37.5A |
30A |
18.8A |
12.5A |
9.4A |
|
CURRENT RANGE |
0 ~ 75A |
0 ~ 75A |
0 ~ 37.5A |
0 ~ 30A |
0 ~ 18.8A |
0 ~ 12.5A |
0 ~ 9.4A |
|
RATED POWER |
247.5W |
375W |
450W |
450W |
451.2W |
450W |
451.2W |
|
RIPPLE & NOISE (max.) Note.2 |
200mVp-p |
200mVp-p |
200mVp-p |
200mVp-p |
200mVp-p |
200mVp-p |
200mVp-p |
|
VOLTAGE ADJ. RANGE |
2.97 ~ 3.63V |
4.5 ~ 5.5V |
10.8 ~ 13.5V |
13.5 ~ 16.5V |
21.6 ~ 28.5V |
32.4 ~ 39.6V |
43.2 ~ 52.8V |
|
VOLTAGE TOLERANCE Note.3 |
±3.0% |
±3.0% |
±1.0% |
±1.0% |
±1.5% |
±1.0% |
±1.0% |
|
LINE REGULATION |
±0.5% |
±0.5% |
±0.3% |
±0.3% |
±0.2% |
±0.2% |
±0.2% |
|
LOAD REGULATION |
±2.0% |
±2.0% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
|
SETUP, RISE TIME |
1500ms, 50ms/230VAC 1500ms, 50ms/115VAC at full load |
|||||||
HOLD UP TIME (Typ.) |
16ms/230VAC 12ms/115VAC at full load |
|||||||
INPUT |
VOLTAGE RANGE |
90 ~ 132VAC / 180 ~ 264VAC selected by SW 254 ~ 370VDC |
||||||
FREQUENCY RANGE |
47 ~ 63Hz |
|||||||
EFFICIENCY (Typ.) |
74% |
78% |
83% |
84% |
86% |
86% |
88% |
|
AC CURRENT (Typ.) |
10A/115VAC 6A/230VAC |
|||||||
INRUSH CURRENT (Typ.) |
35A/115VAC 55A/230VAC |
|||||||
LEAKAGE CURRENT |
<2.5mA / 240VAC |
|||||||
PROTECTION |
OVERLOAD |
105 ~ 150% rated output power |
||||||
Protection type : Shut down o/p voltage, re-power on to recovery |
||||||||
OVER VOLTAGE |
3.8 ~ 4.6V |
5.75 ~ 6.75V |
13.8 ~ 16.2V |
18 ~ 21V |
32 ~ 36V |
45 ~ 52V |
57.6 ~ 67.2V |
|
Protection type : Shut down o/p voltage, re-power on to recovery |
||||||||
OVER TEMPERATURE |
Shut down o/p voltage, recovers automatically after temperature goes down |
|||||||
ENVIRONMENT |
WORKING TEMP. |
-10 ~ +60℃ (Refer to "Derating Curve") |
||||||
WORKING HUMIDITY |
20 ~ 90% RH non-condensing |
|||||||
STORAGE TEMP., HUMIDITY |
-40 ~ +85℃,10 ~ 95% RH |
|||||||
TEMP. COEFFICIENT |
±0.05%/℃ (0 ~ 50℃) |
|||||||
VIBRATION |
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes |
|||||||
SAFETY |
SAFETY STANDARDS |
UL62368-1, EAC TP TC 004, BSMI CNS14336-1 approved |
||||||
WITHSTAND VOLTAGE |
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC |
|||||||
ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH |
|||||||
OTHERS |
MTBF |
200K hrs min. MIL-HDBK-217F (25℃) |
||||||
DIMENSION |
225*124*50mm (L*W*H) |
|||||||
PACKING |
1.25Kg;12PCS/16Kg/1CUFT |
MODEL |
SE-600-5 |
SE-600-12 |
SE-600-15 |
SE-600-24 |
SE-600-27 |
SE-600-36 |
SE-600-48 |
|
OUTPUT |
DC VOLTAGE |
5V |
12V |
15V |
24V |
27V |
36V |
48V |
RATED CURRENT |
100A |
50A |
40A |
25A |
22.2A |
16.6A |
12.5A |
|
CURRENT RANGE |
0 ~ 100A |
0 ~ 50A |
0 ~ 40A |
0 ~ 25A |
0 ~ 22.2A |
0 ~ 16.6A |
0 ~ 12.5A |
|
RATED POWER |
500W |
600W |
600W |
600W |
599.4W |
597.6W |
600W |
|
RIPPLE & NOISE (max.) Note.2 |
150mVp-p |
150mVp-p |
150mVp-p |
150mVp-p |
150mVp-p |
200mVp-p |
200mVp-p |
|
VOLTAGE ADJ. RANGE |
4.75 ~ 5.5V |
10 ~ 13.5V |
13.5 ~ 16.5V |
22 ~ 26.4V |
24 ~ 30V |
32 ~ 40V |
43 ~ 56V |
|
VOLTAGE TOLERANCE Note.3 |
±2.0% |
±1.0% |
±1.0% |
±1.0% |
±1.0% |
±1.0% |
±1.0% |
|
LINE REGULATION |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
|
LOAD REGULATION |
±2.0% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
|
SETUP, RISE TIME |
1000ms, 50ms/230VAC 1000ms, 50ms/115VAC at full load |
|||||||
HOLD UP TIME (Typ.) |
20ms/230VAC 16ms/115VAC at full load |
|||||||
|
VOLTAGE RANGE |
90 ~ 132VAC / 180 ~ 264VAC selected by switch 254 ~ 370VDC |
||||||
FREQUENCY RANGE |
47 ~ 63Hz |
|||||||
EFFICIENCY (Typ.) |
78% |
83% |
84% |
87% |
87% |
87% |
88% |
|
AC CURRENT (Typ.) |
12A/115VAC 7.5A/230VAC |
|||||||
INRUSH CURRENT (Typ.) |
30A/115VAC 60A/230VAC |
|||||||
LEAKAGE CURRENT |
<2.0mA / 240VAC |
|||||||
PROTECTION |
OVERLOAD |
105 ~ 125% rated output power |
||||||
Protection type : Shut down o/p voltage, re-power on to recover |
||||||||
OVER VOLTAGE |
5.75 ~ 6.3V |
13.8 ~ 16.2V |
18 ~ 21V |
27.6 ~ 32.4V |
31 ~ 36.5V |
42 ~ 50V |
57.6 ~ 67.2V |
|
Protection type : Shut down o/p voltage, re-power on to recover |
||||||||
OVER TEMPERATURE |
Shut down o/p voltage, recovers automatically after temperature goes down |
|||||||
ENVIRONMENT |
WORKING TEMP. |
-20 ~ +60℃ (Refer to output load derating curve) |
||||||
WORKING HUMIDITY |
20 ~ 90% RH non-condensing |
|||||||
STORAGE TEMP., HUMIDITY |
-40 ~ +85℃, 10 ~ 95% RH |
|||||||
TEMP. COEFFICIENT |
±0.05%/℃ (0 ~ 50℃) |
|||||||
VIBRATION |
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes |
|||||||
SAFETY & EMC |
SAFETY STANDARDS |
UL60950-1,UL62368-1, EAC TP TC 004, BSMI CNS14336-1, KC K60950-1(for 12V,24V only) approved |
||||||
WITHSTAND VOLTAGE |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
|||||||
ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC |
|||||||
OTHERS |
MTBF |
197K hrs min. MIL-HDBK-217F (25℃) |
||||||
DIMENSION |
247*127*63.5mm (L*W*H) |
|||||||
PACKING |
2.1Kg; 6pcs/13.4Kg/1.03CUFT |
|||||||
NOTE |
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft}. 5. This power supply does not meet the harmonic current requirements outlined by EN61000-3-2. Please do not use this power supply under the following conditions: a} the end-devices is used within the European Union, and b} the end-devices is connected to public mains supply with 220Vac or greater rated nominal voltage, and c} the power supply is: - installed in end-devices with average or continuous input power greater than 75W, or - belong to part of a lighting system Exception: Power supplies used within the following end-devices do not need to fulfill EN61000-3-2 a} professional equipment with a total rated input power greater than 1000W; b} symmetrically controlled heating elements with a rated power less than or equal to 200W 6. Products made in Taiwan do not have KC logo. Please contact MEAN WELL sales for more information. |
MODEL |
SE-1000-5 |
SE-1000-9 |
SE-1000-12 |
SE-1000-15 |
SE-1000-24 |
SE-1000-48 |
|
OUTPUT |
DC VOLTAGE |
5V |
9V |
12V |
15V |
24V |
48V |
RATED CURRENT |
150A |
100A |
83.3A |
66.7A |
41.7A |
20.8A |
|
CURRENT RANGE |
0 ~ 150A |
0 ~ 100A |
0 ~ 83.3A |
0 ~ 66.7A |
0 ~ 41.7A |
0 ~ 20.8A |
|
RATED POWER |
750W |
900W |
999.6W |
1000.5W |
1000.8W |
998.4W |
|
RIPPLE & NOISE (max.) Note.2 |
150mVp-p |
150mVp-p |
150mVp-p |
150mVp-p |
200mVp-p |
200mVp-p |
|
VOLTAGE ADJ. RANGE |
3.3 ~ 5.5V |
7.5 ~ 10V |
10 ~ 13.5V |
13.5 ~ 16.5V |
22 ~ 27.5V |
43 ~ 56V |
|
VOLTAGE TOLERANCE Note.3 |
±1.0% |
±1.0% |
±1.0% |
±1.0% |
±1.0% |
±1.0% |
|
LINE REGULATION |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
|
LOAD REGULATION |
±1.0% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
|
SETUP, RISE TIME |
1500ms, 50ms/230VAC 1500ms, 50ms/115VAC at full load |
||||||
HOLD UP TIME (Typ.) |
20ms/230VAC 15ms/115VAC at full load |
||||||
INPUT |
VOLTAGE RANGE |
90 ~ 132VAC / 180 ~ 264VAC selected by TB2 254 ~ 370VDC |
|||||
FREQUENCY RANGE |
47 ~ 63Hz |
||||||
EFFICIENCY (Typ.) |
81% |
84% |
85% |
86% |
88% |
89% |
|
AC CURRENT (Typ.) |
17.5A/115VAC 10A/230VAC |
||||||
INRUSH CURRENT (Typ.) |
35A/115VAC 55A/230VAC |
||||||
LEAKAGE CURRENT |
<2.5mA / 240VAC |
||||||
PROTECTION |
OVERLOAD |
105 ~ 125% rated output power |
|||||
Protection type : Shut down o/p voltage, re-power on to recover |
|||||||
OVER VOLTAGE |
5.75 ~ 6.75V |
10.4 ~ 12.2V |
13.8 ~ 16.2V |
18 ~ 21V |
28 ~ 32.4V |
57.6 ~ 67.2V |
|
Protection type : Shut down o/p voltage, re-power on to recover |
|||||||
OVER TEMPERATURE |
70℃±5℃ (TSW1) detect on heatsink of power transistor |
||||||
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down |
|||||||
FUNCTION |
DC_OK SIGNAL |
PSU turn on:3.3V ~ 5.6V PUS turn off:0 ~ 1V |
|||||
REMOTE CONTROL |
RC+/RC-: 0 ~ 0.8V power on; 4 ~ 10V power off |
||||||
ENVIRONMENT |
WORKING TEMP. |
-20 ~ +60℃ (Refer to "Derating Curve") |
|||||
WORKING HUMIDITY |
20 ~ 90% RH non-condensing |
||||||
STORAGE TEMP., HUMIDITY |
-40 ~ +85℃, 10 ~ 95% RH |
||||||
TEMP. COEFFICIENT |
±0.05%/℃ (0 ~ 50℃) |
||||||
VIBRATION |
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes |
||||||
SAFETY |
SAFETY STANDARDS |
UL60950-1, BSMI CNS14336-1, EAC TP TC 004 approved |
|||||
WITHSTAND VOLTAGE |
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC |
||||||
ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH |
||||||
OTHERS |
MTBF |
251.6K hrs min. MIL-HDBK-217F (25℃) |
|||||
DIMENSION |
278*127*63.5mm (L*W*H) |
||||||
PACKING |
2.5Kg; 6pcs/16Kg/1.38CUFT |
MODEL |
SE-1500-5 |
SE-1500-12 |
SE-1500-15 |
SE-1500-24 |
SE-1500-27 |
SE-1500-48 |
|
OUTPUT |
DC VOLTAGE |
5V |
12V |
15V |
24V |
27V |
48V |
RATED CURRENT |
300A |
125A |
100A |
62.5A |
55.6A |
31.3A |
|
CURRENT RANGE |
0 ~ 300A |
0 ~ 125A |
0 ~ 100A |
0 ~ 62.5A |
0 ~ 55.6A |
0 ~ 31.3A |
|
RATED POWER |
1500W |
1500W |
1500W |
1500W |
1501.2W |
1502.4W |
|
RIPPLE & NOISE (max.) Note.2 |
150mVp-p |
150mVp-p |
150mVp-p |
150mVp-p |
150mVp-p |
150mVp-p |
|
VOLTAGE ADJ. RANGE |
3.3 ~ 5.5V |
10.8 ~ 13.5V |
13.5 ~ 16.5V |
21.6 ~ 26.4V |
25 ~ 30V |
43.2 ~ 56V |
|
VOLTAGE TOLERANCE Note.3 |
±2.0% |
±1.0% |
±1.0% |
±1.0% |
±1.0% |
±1.0% |
|
LINE REGULATION |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
|
LOAD REGULATION |
±2.0% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
|
SETUP, RISE TIME |
150ms, 12ms / 230VAC at full load |
||||||
HOLD UP TIME (Typ.) |
26ms / 230VAC at full load |
||||||
INPUT |
VOLTAGE RANGE |
180 ~ 264VAC 254 ~ 370VDC |
|||||
FREQUENCY RANGE |
47 ~ 63Hz |
||||||
EFFICIENCY (Typ.) |
81% |
85% |
85% |
87% |
88% |
89% |
|
AC CURRENT (Typ.) |
17.5A / 230VAC |
||||||
INRUSH CURRENT (Typ.) |
60A / 230VAC |
||||||
LEAKAGE CURRENT |
<3.5mA / 240VAC |
||||||
PROTECTION |
OVERLOAD |
105 ~ 125% rated output power |
|||||
Protection type : Shut down o/p voltage, re-power on to recover |
|||||||
OVER VOLTAGE |
5.75 ~ 6.75V |
14.5 ~ 16.2V |
18 ~ 21V |
27.6 ~ 32.4V |
31 ~ 35V |
57.6 ~ 67.2V |
|
Protection type : Shut down o/p voltage, re-power on to recover |
|||||||
OVER TEMPERATURE |
Shut down o/p voltage, recovers automatically after temperature goes down |
||||||
FUNCTION |
DC_OK SIGNAL |
PSU turn on:3.3V ~ 5.6V PUS turn off:0 ~ 1V |
|||||
REMOTE CONTROL |
RC+/RC-: 0 ~ 0.8V power on; 4 ~ 10V power off |
||||||
ENVIRONMENT |
WORKING TEMP. |
-20 ~ +70℃ (Refer to "Derating Curve") |
|||||
WORKING HUMIDITY |
20 ~ 90% RH non-condensing |
||||||
STORAGE TEMP., HUMIDITY |
-40 ~ +85℃, 10 ~ 95% RH |
||||||
TEMP. COEFFICIENT |
±0.05%/℃ (0 ~ 50℃) |
||||||
VIBRATION |
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes |
||||||
SAFETY |
SAFETY STANDARDS |
UL62368-1, BSMI CNS14336-1, EAC TP TC 004 approved |
|||||
WITHSTAND VOLTAGE |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
||||||
ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH |
||||||
OTHERS |
MTBF |
134.5K hrs min. MIL-HDBK-217F (25℃) |
|||||
DIMENSION |
278*177.8*63.5mm (L*W*H) |
||||||
PACKING |
3.3Kg; 4pcs/14.2Kg/1.14CUFT |
||||||
NOTE |
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft}. |
QUESTIONS & ANSWERS
Have a Question?
Be the first to ask a question about this.