MEANWELL RCB Series Rack Mountable Front End Battery Charger
Many In Stock
Ballast /Drivers
RCB-1600-24
S7
Features:
- Charger for lead-acid batteries (Gel, flooded and AGM} and Li-ion batteries (lithium iron and lithium manganese}
- Built-in default 3 stage charging curves and programmable curve
- Built-in I2C interface, PMBus protocol (Optional CANBus protocol}
- Output voltage and current programmable
- Universal AC input / Full range (Withstand 300VAC surge input for 5 seconds}
- Built-in active PFC function
- Forced air cooling by built-in DC fan
- Built-in OR-ing FET, support hot swap (hot plug}
- Active current sharing up to 8000W for one 19” rack shelf
- Protections: Battery under voltage / Battery no connection / Short circuit / Over voltage / Over temperature
- Optional conformal coating
Applications:
- Large scale DC UPS or emergency backup system
- Marine battery charger module
- Electric scooter or vehicle charger station
- Wastewater treatment system
- Electrolysis system
Model Encoding RCB -1600-12-[ ]
RCB---->Series name
1600----->Output wattage
12----->Nominal voltage
[ ]------>Communication protocol option
Type |
Communication Protocol |
Blank |
PMBus protocol |
CAN |
CANBus protocol |
Specification:
MODEL |
RCB-1600-12 |
RCB-1600-24 |
RCB-1600-48 |
|
OUTPUT |
BOOST CHARGE VOLTAGE(Vboost)(default) |
14.4V |
28.8V |
57.6V |
FLOAT CHARGE VOLTAGE(Vfloat)(default) |
13.8V |
27.6V |
55.2V |
|
CONSTANT CURRENT(CC)(default) |
100A |
55A |
27.5A |
|
RATED POWER |
1440W |
1584W |
1584W |
|
VOLTAGE ADJ. RANGE |
By built-in potentiometer, SVR |
|
|
|
11.5 ~ 15V |
23.5 ~ 30V |
47.5 ~ 58.8V |
||
RECOMMENDED BATTERY CAPACITY(AMP HOURS) Note.3 |
330 ~ 1000Ah |
180 ~ 550Ah |
90 ~ 270Ah |
|
LEAKAGE CURRENT FROM BATTERY (Typ.) Note.8 |
<45mA |
|||
INPUT |
VOLTAGE RANGE Note.4 |
90 ~ 264VAC 127 ~ 370VDC |
||
FREQUENCY RANGE |
47 ~ 63Hz |
|||
POWER FACTOR (Typ.) |
0.97/230VAC at full load |
|||
EFFICIENCY (Typ.) |
90.5% |
92% |
93% |
|
AC CURRENT (Typ.) Note.4 |
14A/115VAC 8A/230VAC |
15A/115VAC 8.5A/230VAC |
||
INRUSH CURRENT (Typ.) |
COLD START 35A/230VAC |
|||
LEAKAGE CURRENT |
<1.5mA / 230VAC |
|||
PROTECTION |
OVER VOLTAGE |
15.75 ~ 18.75V |
31.5 ~ 37.5V |
63 ~ 75V |
Protection type : Shut down o/p voltage, re-power on to recover |
||||
OVER TEMPERATURE |
Shut down o/p voltage, recovers automatically after temperature goes down |
|||
FUNCTION |
OUTPUT VOLTAGE PROGRAMMABLE(PV) Note 5 |
Adjustment of output voltage is allowable to 75 ~ 125% of nominal output voltage Please refer to the Function Manual. |
||
OUTPUT CURRENT PROGRAMMABLE(PC) Note 5 |
Adjustment of output current is allowable to 20 ~ 100% of rated current Please refer to the Function Manual. |
|||
AUXILIARY POWER |
5V @ 0.3A, 12V @ 0.8A |
|||
REMOTE ON-OFF CONTROL |
By electrical signal or dry contact Power ON:short Power OFF:open. Please refer to the Function Manual |
|||
TEMPERATURE COMPENSATION |
-3mV / ℃ / cell / (12V = 6 cells ; 24V = 12 cells ; 48V = 24 cells) |
|||
DC OK SIGNAL |
The isolated TTL signal out. Please refer to the Installation Manual |
|||
AC OK SIGNAL |
The isolated TTL signal out. Please refer to the Installation Manual |
|||
ENVIRONMENT |
WORKING TEMP. |
-30 ~ +70℃ (Refer to "Derating Curve") |
||
WORKING HUMIDITY |
20 ~ 90% RH non-condensing |
|||
STORAGE TEMP., HUMIDITY |
-40 ~ +85℃, 10 ~ 95% RH non-condensing |
|||
TEMP. COEFFICIENT |
±0.03%/℃ (0 ~ 50℃) |
|||
VIBRATION |
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes |
|||
SAFETY & EMC (Note 6) |
SAFETY STANDARDS |
UL60950-1, TUV EN60950-1, EAC TP TC 004 approved |
||
WITHSTAND VOLTAGE |
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:1.5KVAC (0.5KVAC for 12V) |
|||
ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH |
|||
EMC EMISSION |
Compliance to EN55032 (CISPR32) Conduction Class B, Radiation Class A ; EN61000-3-2,-3, EAC TP TC 020 |
|||
EMC IMMUNITY |
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 (EN50082-2), Heavy industry level, criteria A, EAC TP TC 020 |
|||
OTHERS |
MTBF |
160.1K hrs min. Telcordia SR-332 (Bellcore) ; 38.9K hrs min. MIL-HDBK-217F (25℃) |
||
DIMENSION |
300*85*41mm (L*W*H) |
|||
PACKING |
1.87Kg; 6pcs/12.2Kg/1.16CUFT |
|||
NOTE |
1. Modification for charger specification may be required for different battery specification. Please contact battery vendor and MEAN WELL for details. 2. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. 3. This is MEAN WELL's suggested range. Please consult your battery manufacturer for their suggestions about maximum charging current limitation. 4. Derating may be needed under low input voltages. Please check the derating curve for more details. 5. PV/PC functions when users are not operating on PMBus/CANBus. SVR functions when users are neither operating on PMBus/CANBus nor using PV/PC. 6. The charger is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on a 720mm*360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com} 7. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft}. 8. When charging lead acid battery or battery without BMS, use breaker to disconnect charger and battery after fully charged. |
Dimensions:
L * W * H
300 * 85 * 41 (1U} mm
11.8 * 3.35 * 1.61 (1U} inch